• products
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

ZN63C-12
Picture
  • ZN63C-12
  • ZN63C-12

ZN63C-12

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

Selection

ZN63 C - 12 P / T 630 - 25 FT R P210
Name Structure - Rated   voltage(KV) Pole / Operating  mechanism Rated    current(A) - Rated short-circuit Installation Main circuit Phase   distance
type
Indoor vacuum circuit    breaker Side operation - 12:12KV No mark: Insulatingcylinder type P: Solid-sealing type / T:Spring type 630 1250 1600 2000 2500 3150 4000 - 20 25 31.5 40 FT:Fixed type L: Left R:  Right P210

Note:
1. order a ZN63 side-mounted main circuit with right wiring, rated voltage 12KV, rated current 630A, rated short-circuit breaking current 25KA.

Operating conditions

1. The ambient temperature is not higher than +40°C and not lower than -15°C (storage and transportation at -30°C are allowed); 2. The altitude is not higher than 1000m;
3. Relative temperature: the daily average is not more than 95%, and the monthly average The value is not more than 90%, the daily average value of saturated vapor pressure is not more than 2.2×10-'MPa, and the monthly average value is not more than 1.8×10MPa;
4. The seismic intensity does not exceed 8 degrees;
5. There is no fire, explosion hazard, serious pollution, Places subject to chemical corrosion and severe vibration.

Features

1. The arc extinguishing chamber and operating mechanism of the circuit breaker are arranged in a front-to-back configuration and connected as a whole through a transmission mechanism.
2. Depending on the design of the switchgear, the primary conductive output can be divided into right output and left output.
3. The main conductive circuit is primarily designed with an insulating cylinder, but it can also be designed with a fixed-sealing pole method.
4. The operating mechanism adopts a spring energy storage type and has both electric and manual energy storage functions.
5. It features an advanced and rational buffering device, ensuring no rebound during circuit interruption and reducing the impact and vibration during circuit breaking.
6. It requires minimal or no adjustments and requires very little maintenance or is maintenance-free.
7. The mechanical lifespan can reach 20,000 cycles.

Technical data

Technical datas are shown in Table 1

Item Unit Value
Rated voltage KV 12
Rated Rated lightning impulse withstand voltage (peak) 78(Phase-to-phase),80(Phase-to-phase)
insulation level 1min power frequency withstand voltage 42(Phase-to-phase),48(Phase-to-phase)
Rated short-circuit breaking current(KA) KA 25 31.5
Rated current A 6,301,250 63,012,501,600
Rated thermal stable current (effective value) KV 25 31.5
Rated dynamicstable current (peak value) 63 80
Rated short-circuit making current (peak value) 63 80
Rated short-circuit breaking current breaking times Times 50
Secondary circuit power frequency withstand current V/min 2000
Rated operating sequence "Opening -0.3s - closing and openin g -180s - closing and opening "
Rated thermal stability time S 4
Rated single/back to back capacitor bank breaking current A 630/400
Mechanical life 20000

The mechanical characteristic parameters are shown in Table 2

Item Unit Value
Contact distance mm 11±1,9±1(Solid sealing type)
Contact travel 3.5±1
Average closing speed (6mm~contact closed) m/s 0.4~0.8
Average opening speed (contact separation -6mm) 0.9~1.3
Opening time (rated voltage) ms 20~50
Closing time (rated voltage) 35~70
Contact closing bounce time ms ≤2
Three phase opening asynchrony ≤2
Allowable cumulative thickness of wear for
moving and stationary contacts
mm 3
ain electrical circuit resistance μ Ω ≤(630A),≤ 45( 1250A)
Contact pressure of closing contacts N 2400±200( KA), 3100±200( 31.5KA)

Opening and closing coil parameters are shown in Table 3

Item Closing coil Opening coil Value
Rated operating voltage AC110/220 AC110/220 The opening coilshall not   open when it is less than    30% of the rated operating voltage
DC110/220 DC110/220
Coil power 264 264
Normal operating voltage range 85% -110% rated voltage 65% -120% rated voltage

Energy storage motor parameters are shown in Table 4

Model Rated voltage Rated input power Normal operating voltage Energy storage time at rated voltage
( V ) ( W ) ( V ) ( S )
ZYJ55-1 DC110 50~75 85% -110% rated voltage ≤15
CD220

Overall and mounting dimensions(mm)

Fixed outline size drawing (insulation cylinder)

1

1

Solid seal type outline dimension drawing (insulation cylinder)

1

1

 

 

 

 

 

 

 

 

Write your message here and send it to us

Data Download