• products
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

ZN63(VS1)-12
Picture
  • ZN63(VS1)-12
  • ZN63(VS1)-12

ZN63(VS1)-12

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

Selection

ZN63 - 12 T 630 - 25 HT P210
Model Rated
voltage(KV)
Operating  mechanism Rated    current(A) Rated short-circuit   breaking current(KA) Installation Phase spacing
Indoor vacuum circuit breaker 12:12KV T: Spring type 630,1250,
1600, 2000,
2500, 3150,
4000
20, 25,
31.5, 40
HT: Handcart
FT: Fixed type
P150,
P210,
P275

Note:
ZN63-12 adopts a double spring integrated mechanism by default. If a single spring modular mechanism is required, a single spring needs to be added to the model backup;

Operating conditions

1.The ambient temperature is not higher than +40°C and not lower than -15°C (storage and transportation at -30°C are allowed);
2. The altitude is not higher than 1000m;
3.Relative temperature: the daily average is not more than 95%, and the monthly average The value is not more than 90%, the daily average value of saturated vapor pressure is not more than 2.2×10-'MPa, and the monthly average value is not more than 1.8×10MPa;
4.The seismic intensity does not exceed 8 degrees;
5.There is no fire, explosion hazard, serious pollution, Places subject to chemical corrosion and severe vibration.

Features

1.The arc extinguishing chamber and operating mechanism of the circuit breaker are arranged in a front-to-back configuration and connected as a whole through a transmission mechanism.
2.The insulating cylinder is formed using the APG (Automatic Pressure Gelation) new process.
3.Inner skirts and reinforcing ribs are added to the insulating cylinder, which enhances the insulation level and the ability to withstand dynamicstable currents.
4.The vacuum arc extinguishing chamber is installed inside the insulating cylinder, effectively preventing damage and surface contamination caused by foreign objects, while reducing the overall size of the circuit breaker.
5.The operating mechanism adopts a spring-stored energy design, providing both electric and manual energy storage functions.
6.An advanced and rational buffer device ensures that there is no rebound during disconnection, reducing disconnection impact and vibration.
7.No adjustment needed and has minimal maintenance or maintenance-free operation.
8.The mechanical lifespan can reach up to 20,000 operations

 Technical data

Item Unit Value
Rated voltage 12
Rated insulation level Rated lightning impulse withstand voltage (peak) kV 75
1min power frequency withstand voltage 42
Rated current A 630 630, 1250, 1600, 1250, 1600, 2000,
1250 2000, 2500, 3150 2500, 3150, 4000
Rated short circuit breaking current(KA) kA 20 25 31.5 40
Rated thermal stable current (effective value) 20 25 31.5 40
Rated dynamicstable current (peak value) kA 20 63 80 100
Rated short-circuit making current (peak value) 50 63 80 100
Rated short-circuit breaking current breaking times Times 30 30 30
Secondary circuit power frequency withstand current V 2000
Rated operating sequence / Opening -0.3s - closing and opening -
180s - closing and opening -180s - closing
and opening -180s - closing and opening (40kA)
Rated thermal stability time s 4
Rated single/back to back capacitor bank breaking current A 630/400 800/400
Mechanical life Times 20000 10000

The mechanical characteristic parameters of the circuit breaker are shown in Table 2

Item Unit Value
Contact distance mm 11±1(Solid-sealing 9±1)
Contact travel 3.3±0.6
Average closing speed (6mm~contact closed) m/s 0.6±0.2
Average opening speed (contact separation -6mm) m/s 1.2±0.2
Opening time (rated voltage) m/s 20~50
Closing time (rated voltage) 35~70
Contact closing bounce time m/s ≤2 ≤3(40kA)
Three phase opening asynchrony ≤2
Allowable cumulative thickness of wear for moving and stationary contacts mm 3
Main electrical circuit resistance μΩ ≤50(630A)                 ≤45(1250A)
≤35(1600~2000A)  ≤25(2500A and above)
Contact pressure of closing contacts N 2000±200(20kA)  3100±200(31.5kA) 2400±200(25kA) 4500±250(40kA)

The opening and closing coil parameters are shown in Table 3

Item Closing coil Opening coil Note
Rated operating voltage(V) AC110/220,DC110/220 AC110/220,DC110/220 The opening coilshall not open when it is less than 30% of
Coil power(W) 245 245 the rated operating voltage
Normal operating voltage range 85% -110% rated voltage 65% -120% rated voltage

Energy storage motor parameters are shown in Table 4

Model Rated voltage Rated input power Normal operating voltage range Energy storage time at rated voltage
ZYJ55-1 DC110 70 85% -110% rated voltage ≤15
DC220

Overall and mounting dimensions(mm)

Figure 1: Handcart type ZN63 (VS1) circuit breaker suitable for 800mm cabinet width overall dimensions

1

 

 

Rated current (A) 630 1250 1600
Rated short-circuit breaking current(KA) 20,25,31.5 25,31.5,40 31.5,40
Matching static contact dimensions(mm) Φ35 Φ49 Φ55

Figure 2: Fixed type ZN63A (VS1) circuit breaker suitable for 800mm cabinet width overall dimensions

1

Rated current (A) 630 1250 1600
Rated short-circuit breaking current(KA) 20, 25, 31.5 25, 31.5, 40 31.5, 40

Figure 3: Handcart type ZN63A (VS1) circuit breaker suitable for 1000mm cabinet width overall dimensions

1

Rated current (A) 1600 2000 2500 3150 4000
Rated short-circuit breaking current(KA) 31.5, 40 31.5, 40 40
Matching static contact dimensions(mm) Φ79 Φ109

Figure 4: Fixed type ZN63A (VS1) circuit breaker suitable for 1000mm cabinet width overall dimensions

1

 

 

 

 

 

 

Write your message here and send it to us

Data Download