Product Overview
Product Details
Data Download
Related Products
Conatct Us
1. Ambient temperature: upper limit +40℃, lower limit -30℃;
2. Altitude: ≤2000m;
3. Wind pressure: not more than 700Pa (corresponding to the wind speed 34m/s);
4. Earthquake intensity: do not exceed 8 degree;
5. Pollution grade: III class;
6. Maximum daily temperature variety less than 25℃ .
Item | Unit | Parameter | ||
Rated voltage | kV | 12 | ||
Rated | 1min power frequency withstand voltage | Dry test | kV | 42/ fracture 48 |
insulation level | Wet test | kV | 34 | |
Lightning impulse withstand voltage (peak) | kV | 75/ fracture 85 | ||
Rated current | A | 630, 1250 | ||
Rated short-circuit breaking current | kA | 20 | ||
Rated short-circuit breaking current time | Times | 30 | ||
Rated short-circuit closing current (peak) | kA | 50 | ||
Rated peak withstand current | kA | 50 | ||
Rated short-time withstand current | kA | 20 | ||
Rated short circuit duration | S | 4 | ||
Opening time | ms | <50 | ||
Closing time | ms | <60 | ||
Full off time | ms | ≤100 | ||
Arcing time | ms | ≤50 | ||
Mechanical life | Times | 30000 | ||
Switch on power | J | 70 | ||
Rated operational voltage and auxiliary | V | DC 220 | ||
circuits rated voltage | V | AC 220 |
Circuit breaker and mounting dimensions
Controller outline and mounting dimensions