• products
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

ZN85-40.5
Picture
  • ZN85-40.5
  • ZN85-40.5

ZN85-40.5

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

Selection

Operating conditions

1. Ambient temperature -10℃ ~ +40℃
2. Altitude ≤ 1500m;
3. Relative humidity: the daily average is not greater than 95%, the monthly average is not greater than 90%, the daily average of saturated steam is not greater than 2.2* 10- ³Mpa, and the monthly average is not greater than 1.8* 10- ³Mpa;
4. The earthquake intensity does not exceed 8 degrees;
5. Places free of fire, explosion hazards, severe pollution, chemical corrosion and severe vibrations.

Features

1. Adopt the lead screw propulsion mechanism, labor saving, stable, good self-locking performance.
2. Small volume, flexible operation, with characters of reliable electrical performance, long service life, easy maintenance, low maintenance.

 

Installation

1. The installation form of ZN85 vacuum circuit breaker in switch cabinet can be fixed, can also be drawout style, has good interchangeability.
2. This series handcart type circuit breaker is mainly used for 1400mmKYN61 ground cabinet, fixed type circuit breaker is used for XGN-40.5, GG1A-40. 5 and box type substation etc..

Actuator

1. Vacuum circuit breaker ZN85 using the integral type 3AV3 spring operating mechanism, mechanism is relatively mature, stable and reliable.
2. Mechanism design is simple, the output curve and the performance is more suitable for the characteristics and requirements of 40.5kV vacuum circuit breaker.

Technical data

Item Unit Parameter
Parameters of voltage, current, life
Rated voltage kV 40.5
Rated short time power frequency withstand voltage (1min) kV 95
Rated lightning impulse withstand voltage (peak) kV 185
Rated frequency Hz 50
Rated current A 630, 1250, 1600, 2000 2500
Rated short-circuit breaking current kA 25 31.5
Rated short-time withstand current (RMS) kA 25 31.5
Rated peak withstand current kA 63 80
Rated short-circuit closing current kA 63 80
Rated single / back-to-back capacitor A 600/400
bank breaking current
Rated short-circuit current duration S 4
Rated short-circuit current breaking Times Times 20
Rated operating sequence O-0.3s-CO-180s-CO
The main galvanic circle resistance μΩ ≤65
Rated operation voltage AC/DC≌ 220/110
Mechanical life Times ≥10000
Mechanical property parameters
Open clearance between contacts mm 18±1
Overtravel mm 5±1
Contact closing bounce time ms ≤3
Three-phase, switching synchronism ms ≤2
Average opening speed m/s 1.7±0.2
Average closing speed m/s 0.75±0.2
Opening time (rated voltage) ms ≤90
Closing time (rated voltage) ms ≤60
Allowable wear thickness for dynamic and static contact mm 3

Overall and mounting dimensions(mm)

External dimensions of insulating cylinder type

1

Rated current(A) 630 1250 1600 2000 2500
Rated short-circuit breaking current (kA) 20/25/31.5 31.5
Equipped static contact size (mm) Φ35 Φ49 Φ55 Φ79 Φ109
Plum-blossom contacts CT-30 CT-30 CT-36 CT-48 CT-64

Dimensions of solid seal type

1

Rated current(A) 630 1250 1600 2000 2500
Rated short-circuit breaking current (kA) 20/25/31.5 31.5
Equipped static contact size (mm) Φ35 Φ49 Φ55 Φ79 Φ109
Plum-blossom contacts CT-30 CT-30 CT-36 CT-48 CT-64

 

 

 

 

 

Write your message here and send it to us