Product Overview
Product Details
Data Download
Related Products
Conatct Us
General
1.Overload protection
2.Short circuit protection
3.Controlling
4.Used in residential building,non-residential building,energy source industry and infrastructure
Selection
Type | Test current | ripping time | Expected result |
C,D | 1.05In | t≤1h(In≤63A),t≤2h(In>63A) | Not tripping |
C,D | 1.3In | t≤1h(In≤63A),t≤2h(In>63A) | Tripping |
C,D | 2.55In | 1s<t<120s | Tripping |
C | 8In×80% | t≤0.2s | Not tripping |
D | 12In×80% | t≤0.2s | Not tripping |
C | 8In×120% | t<0.2s | Tripping |
D | 121n×120% | t<0.2s | Tripping |
Technical data
Type | Standard | IEC/EN 60947-2 | |
Electrical features | Rated current In | A | 63,80,100,125 |
Poles | 1,2,3,4 | ||
Rated voltage Ue | V | 230/400 | |
Insulation voltage Ui | V | 500 | |
Rated frequency | Hz | 50/60 | |
Rated breaking capacity | A | 6000 | |
Rated impulse withstand voltage(1.2/50)Uimp | V | 6000 | |
Dielectric test voltage at ind.Freq.for 1min | kv | 2.5 | |
Pollution degree | 3 | ||
Thermo-magnetic release characteristic | (C)li=8In.(D)Ii=12lr | ||
Mechanical features | Electrical life | 1500 | |
Mechanical life | t | 10000 | |
Contact position indicator | Yes | ||
Protection degree | IP20 | ||
Reference temperature for setting | 30 | ||
of thermal element | |||
Ambient temperature | ℃ | 5~+40(Special application please refer to temperature compensation correction) | |
(with daily average ≤35℃) | |||
Storage temperature | ℃ | -25~+70 | |
Installation | Terminal connection type | ℃ | Cable/Pin-type busbar |
Terminal size top /bottom for cable | mm² | 50 | |
AWG | 18-1/0 | ||
Terminal size top /bottom for busbar | mm² | 50 | |
AWG | 18-1/0 | ||
Tightening torque | N*m | 3.5 | |
In-Ibs | 31 | ||
Mounting | On DIN rail EN60715(35mm)by means of fast clip device | ||
Connection | From top and bottom |
Overall and mounting dimensions(mm)