• products
  • Product Overview

  • Product Details

  • Data Download

  • Related Products

YCM1LE Earth Leakage MCCB
Picture
  • YCM1LE Earth Leakage MCCB
  • YCM1LE Earth Leakage MCCB
  • YCM1LE Earth Leakage MCCB
  • YCM1LE Earth Leakage MCCB
  • YCM1LE Earth Leakage MCCB
  • YCM1LE Earth Leakage MCCB

YCM1LE Earth Leakage MCCB

1. Overload protection
2. Short circuit protection
3. Controlling
4. Used in residential building, non-residential building, energy source industry and infrastructure.
5. According to the type of instantaneous release classified as follows : type B(3-5)ln, type C(5-10)ln, type D(10-20)ln

Conatct Us

Product Details

product-description1

Note

Without current release components, N-Pole is alwaus at making status, not makes and breaks with other three poles;
Without current release components, N-Pole makes with the other three poles(NPole first makes then breaks);

Technical data
Type YCM1LE-125 YCM1LE-250 YCM1LE-400 YCM1LE-630
YCM1LE-800
Frame current  Inm(A) 125 250 400 630
800
Rated current  In(A) 10, 16, 20, 25, 32, 40,50, 63, 80, 100, 125 100, 125, 140, 160,180, 200, 225, 250 225, 315, 350, 400 400, 500, 630
630, 700, 800
Pole 2 3 4 2 3 4 3 4 3 4
Rated insulation voltage AC800
Ui(V)
Rated working voltage AC400
Ue(V)
Rated impulse withstand 8000
voltage  Uimp(V)
Arcing-over distance 50 100
(mm)
Breaking ability level L M L M L M L M
Rated ultimate short-circuit 35 50 35 50 50 65 50 65
breaking capacity  Icu(kA)
Rated working short-circuit 22 25 22 25 35 42 35 42
breaking capacity  Ics(kA)
Rated residual short-circuit 7.5 12.5 7.5 12.5 12.5 13.5 12.5 13.5
breaking capacity
Rated residual operating current  IΔn(mA) No time-delay type 30/100/500/100/300/500 30/100/500/100/300/500 100/300/500 300/500/1000
Time-delay type 100/300/500 100/300/500 100/300/500 300/500/1000
Rated residual unoperating current  IΔn(mA) 1/2 IΔn 1/2 IΔn 1/2 IΔn 1/2 IΔn
Operating performance (times) Power on 1500 1000 1000 1000
Power off 8500 7000 4000 4000
Total times 10000 8000 5000 5000
Residual current protection opreating time IΔn 2IΔn 5IΔn 10IΔn
Max. breaking time(s) No time-delay type 0.2 0.1 0.04 0.04
Time-delay 0.4/1 0.4/1 0.3/1 0.3/1
type
Release method and accessories code Accessories installation and down-leads
Accessories name Electromagnetic release Complex release YCM1LE-125/3 YCM1LE-250/3 YCM1LE-125/4 YCM1LE-250/4 YCM1LE-400/3 YCM1LE-630/3 YCM1LE-800/3 YCM1LE-400/4 YCM1LE-630/4 YCM1LE-800/4
Without parts 200 300
Alarm contact 208 308
Shunt release 210 310
Auxiliary contact 220 320
Undervoltage release 230 330
Shunt release,Auxiliary contact 240 340
Secondary auxiliary contact 260 360
Auxiliary contact,Undervoltage release 270 370
Shunt release,Alarm contact 218 318
Auxiliary contact, 228 328
Alarm contact
Undervoltage release, Alarm contact 238 338
Shunt release,Auxiliary contact,Alarm contact 248 348
Secondary auxiliary contact,Alarm contact 268 368
Auxiliary contact,Undervoltage release,Alarm contact 278 378

 

Type Pole Overall size (mm) Installation size (mm)
A B C D a b Φd
YCM1LE-125 3 92 150 110 92 30 129 4.5
4 122 60
YCM1LE-250 3 107 165 110 90 35 126 4.5
4 142 70
YCM1LE-400 3 150 257 146.5 106.5 44 194 7
4 198 94
YCM1LE-630 YCM1LE-800 3 210 280 155 115.5 70 243 7
4 280 140
Write your message here and send it to us

Data Download